Industrial Sensors
  Current Sensors
MI-3240-CTS
 
  AC Current Sensors-MI-3200-SC200
 
 

Microcomm's AC Current Sensors series MI-3200-SC200 Connect directly to any Data Logger input channel. Also connects directly to any recorder or data acquisition system that has a 0-5vdc input. No external power required. Split core construction simplifies installation on existing conductor. Nylon thumb screws, no exposed metal parts; Monitor motors, pumps, or any AC load.

 
Features:
  • Split core design
  • Self powered
  • Rugged plastic housing
  • Output signal is accurate even at very low input current levels (below 1% of full scale).
Technical Specifications:  
Input Current - AC Current, single phase, 50 - 400 Hz, load power factor 0.5 to 1.0 lead or lag.  
Accuracy - ±2.0% of reading from 2.5 % to 100% of full scale.
±4% of reading at 1% of full scale.
 
Bandwidth - 10-1000Hz (within ±3db)  
Temperature Effect - ±0.05% (-20 to 85°C)  
Response time - 250 milliseconds (input from 10% to 90% of full scale).  
Ripple - 0.5%  
Voltage rating - 600 Vac. Tested with full wave 10KV impulse for 60 seconds.  
Overload - 1.6x full scale (continuous).  
Surge - 3x full scale.  
Lead wires - 8 ft (2.4 meter) signal cable.  
Output signal - Linear 0 - 5vdc  
Low range usability   To below 0.1% of full scale.
Overall size  
Add 2" to Window size in table below for overall length and height dimension (Add 2.5" for SC1500A).
Overall width 1.25" (includes nylon thumbscrews)

  AC Current Sensors-MI-3200-DC100A
 
 

Microcomm's AC Current Sensors series MI-3200-DC100A Connect directly to any Data Logger input channel. No external power required. Also connects directly to any recorder or data acquisition system with a 0-5vdc input and 5vdc excitation.

 
Features:
  • Single 5vdc supply, consumes less than 10ma
  • Self powered
  • Rugged plastic housing
  • Output signal is accurate even at very low input current levels (below 1% of full scale).
Technical Specifications:  
Total output error - ±1% of full scale at 25°C
 
Range ±50 amps dc
Zero offset - ±0.15% of F.S. maximum (-40 to 80°C)
 
Temperature effect on span - ±0.10% of F.S. per °C  
Response time - 2 milliseconds (dc current change from 10% to 90% of full scale).  
Isolation voltage - 3kVRMS minimum (current terminals to signal cable lead wires)  
Surge rating (all models) - 300 amps for 10 second pulse, 10% maximum duty cycle for repetitive pulses.
800 amps for 1 second pulse, 1% maximum duty cycle for repetitive pulses.
 
Continuous over current (all models) - 180 amps  
Power requirements - 5vdc (±10%), 10ma max  
Output signal vs supply voltage - Output signal ratiometric to supply voltage  
Warm-up time - 10 milliseconds (time from power applied until output signal is valid).  
Output signal - Linear 0.5 - 4.5vdc (0 amps = 2.5v)  
Signal cable leads   Four: Ground, +5v supply, Signal output, Shield drain wire. (shield drain wire has no internal connection inside sensor).
Signal cable length  
10 ft (3 meter)
Operating temperature range   -40°C to 80°C (-40°F to 176°F)
Overall size   3.50" long, 2.55" wide, 1.25" high
89mm x 65mm x 32mm high
DC current terminals   Two 1/4-20 aluminum studs, with nuts and lock washers. Suitable for ring terminals (ring terminals not supplied).
Mounting holes   Two 0.19"dia. holes, 3.0" O.C.